String current up to 20A, perfectly match large current modules
Built-in Backup Port with Automatic UPS switching
10 second 200% surge power backup overload capability
6 customisable charge/discharge time settings
Generator connectivity with multiple input methods and automatic generator On/Off control
Supports 1ph and 3ph flexible connection with max 96kW in parallel
Supports peak shaving control in both "self-use" and "generator" mode
Intelligent AC coupling scheme, easily upgrade existing grid-connected systems
S6-EH1P12K-L
S6-EH1P14K-L
S6-EH1P16K-L
Models | 12K | 14K | 16K |
Input DC (PV side) | |||
Recommended max. PV power | 16.8 kW | 19.6 kW | 22.4 kW |
Max. input voltage | 550 V | ||
Rated voltage | 380 V | ||
Start-up voltage | 100 V | ||
MPPT voltage range | 80-520 V | ||
Max. input current | 40 A / 40 A / 40 A | ||
Max. short circuit current | 50 A / 50 A / 50 A | ||
MPPT number/Max. input strings number | 3/6 | ||
Battery | |||
Battery type | Li-ion / Lead-acid | ||
Battery voltage range | 40 - 60 V | ||
Max. charge / discharge power | 12 kW | 14 kW | 16 kW |
Communication | CAN/RS485 | ||
Output AC (Grid side) | |||
Rated output power | 12 kW | 14 kW | 16 kW |
Max. apparent output power | 12 kVA | 14 kVA | 16 kVA |
Operation phase | L/N/PE | ||
Rated grid voltage | 220 V / 230 V | ||
Rated grid frequency | 50 Hz / 60 Hz | ||
Rated grid output current | 54.5 A / 52.2 A | 63.6 A / 60.9 A | 72.7 A / 69.6 A |
Max. output current | 54.5 A / 52.2 A | 63.6 A / 60.9 A | 72.7 A / 69.6 A |
Power factor | 1.0 | ||
THDi | <3% | ||
Input AC (Grid side) | |||
Input voltage range | 187-253 V | ||
Max. input current | 110 A | ||
Frequency range | 45-55 HZ/55-65 HZ | ||
Output AC (Back-up) | |||
Rated output power | 12 kW | 14 kW | 16 kW |
Max. apparent output power | 2 times of rated power, 10 S | ||
Back-up switch time | <4 ms | ||
Rated output voltage | L/N/PE, 220 V / 230 V | ||
Rated frequency | 50 Hz / 60 Hz | ||
Rated output current | 54.5 A / 52.2 A | 63.6 A / 60.9 A | 72.7 A / 69.6 A |
Max. output over current protection, 10 sec | 109 A | 127 A | 145 A |
Max. Continuous AC Passthrough | 100 A | ||
THDv (@linear load) | <3% | ||
Max. number of parallel | 10 | ||
Input Generator | |||
Max. input power | 12 kW | 14 kW | 16 kW |
Max. input current | 54.5 A | 63.6 A | 72.7 A |
Rated input frequency | 50 Hz / 60 Hz | ||
Efficiency | |||
Max. efficiency | 97.6% | ||
EU efficiency | 97.2% | ||
BAT charged by PV Max. efficiency | > 94.9% | ||
BAT charged/discharged to AC Max. efficiency | > 94.33%/93.51% | ||
Protection | |||
Surge protection | Yes | ||
DC reverse-polarity protection | Yes (PV only) | ||
Ground fault monitoring | Yes | ||
Integrated AFCI (DC arc-fault circuit protection) | Yes (1) | ||
Protection class/Over voltage category | I/II | ||
General Data | |||
Dimensions (W*H*D) | 464*763*282 mm | ||
Weight | 48.5 kg | ||
Topology | Transformerless | ||
Operating ambient temperature range | -40 ~ +60°C | ||
Ingress protection | IP66 | ||
Cooling concept | Intelligent redundant fan-cooling | ||
Max. operation altitude | 4000 m | ||
Grid connection standard | NRS 097-2-1, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530 | ||
Safety/EMC standard | IEC/EN 62109-1/-2, EN 61000-6-2/-3 | ||
Features | |||
DC connection | MC4 plug (PV port) / Terminal Block (BAT port) | ||
AC connection | Terminal Block | ||
Interface | LED indicator lights, Bluetooth/Phone app | ||
Communication | RS485, Optional: Wi-Fi, LAN |